A London Fire Brigade investigation into a residential high-rise fire in Poplar revealed that the building’s ventilation systems failed to clear toxic smoke from escape routes putting the lives of residents at risk.

In a report published on 1 June, fire investigators found that smoke detectors on the floor of the fire failed to operate the Automatic Opening Vent (AOV) and the cross-corridor fire doors. This meant that the smoke collected in the hallways and prevented the safe escape of people in the neighboring flats.

Smoke ventilation system

London Fire Brigade Deputy Commissioner - Richard Mills said: "The smoke ventilation system inside New Providence Wharf acted like a broken chimney, leading to a potentially life-threatening situation. Had it not been for the exceptional actions of our firefighters and 999 control officers this could have had tragic consequences.”

Firefighters helped 35 residents leave the building, where the fire started on the 8th floor. Twenty-two of the residents used fire escape hoods so that they could leave the building safely, guided by firefighters in breathing apparatus.

Phase 1 Report

Fire investigators found that the fire started in a fuze box in one of the flats on the 8th floor

One of the recommendations from the Phase 1 Report of the Grenfell Tower Inquiry was for all fire and rescue services to buy fire escape hoods. London has used them since 2018.

Fire investigators found that the fire started in a fuze box in one of the flats on the 8th floor and was burning for some time before being discovered and the alarm raised. Smoke left the flat through a fire door that had been accidentally left open and entered the hallways between flats on the same floor.

Fire safety in high-rise buildings

The fire spread from the eighth floor up to the eleventh floor and the report said: "This is believed to have been facilitated by timber decking on the balconies- but not ACM panels." The building has some ACM cladding but the fire investigation report found it: “Did not significantly contribute to the external spread of fire.” 

Mr. Mills added: “Despite our response to this fire and drawing on the many lessons learned from the Grenfell Tower fire, in many cases we are sadly still not seeing a culture change in all those responsible for fire safety in high-rise buildingsThe New Providence Wharf fire needs to be an urgent wake-up call to all building owners and managers. Look at the fire safety solutions inside your building and take action if they are not performing correctly. It is too late to wait for a fire to see if they work.”

Download PDF version Download PDF version

In case you missed it

Johnson Controls: New Simplex 4017ES Launch
Johnson Controls: New Simplex 4017ES Launch

Johnson Controls, the pioneer for smart, healthy, and sustainable buildings, launches the new Simplex 4017ES Fire Alarm Control Unit to help customers meet evolving life safety voi...

How To Select The Right Door Closer: A Technical Guide
How To Select The Right Door Closer: A Technical Guide

Fire doors are designed to save lives. When closed, they form a crucial barrier against smoke and fire and provide vital time for occupants to escape in an emergency situation. An...

Darley Firefighting Catalog 2025: Innovative Solutions
Darley Firefighting Catalog 2025: Innovative Solutions

Darley has just released Firefighting Equipment Catalog #278! Specifically crafted for first responder professionals, this redesigned catalog features over 200 pages of innovative...

vfd